3/4" Drive Unit (Straight Shank). The stud is driven into the hole with a standard hammer drill using the drive unit.
*When ordering the Capsule Anchor System, you must order the capsules, stud assemblies and drive unit separately. Capsules are sold in packages. Stud assemblies and drive units are sold individually.
Unisorb Anchor Bolt System | |
Anchor Size | 3/4" |
Capsule Number | C-34 |
Drill Diameter | 7/8" |
Hole Depth | 6 5/8" |
Anchor Number & Length | S-34 x 9 1/2" |
Allowable Tensile Load | 8,455 lbs* *Tensile loads are based on 4:1 safety factor applied to the tested bond strength of the adhesive to 4,000 psi concrete. |
Allowable Shear Load | 4,355 lbs* *Shear loads are based on an F 1554 Gr. 36 anchor and based on the methods described in the AISC Manual of Steel Construction (Ninth Edition). Greater allowable loads are possible by using different anchor materials and by altering the embedment depth. |
To Install: | To install the anchor a clearance hole is prepared and a capsule is inserted. The stud is driven into the hole with a standard hammer drill using the drive unit. This action breaks the glass capsule and mixes the premeasured components. At room temperature the anchor nuts may be torqued down within approximately 30 minutes. |